Beckett · Boiler troubleshooting

NX burner: oil supply rules (pump seal leaks, air in line, plugged nozzle)

Beckett NX

What is going on

Most NX oil-side problems come from the supply piping. Check it against these rules.

Likely causes

  • Bypass plug in a one-pipe system (blows the pump seal)
  • Inlet pressure over 3 psig on gravity feed
  • Valve installed in the return line
  • Compression fittings or Teflon tape pieces in the line
  • Lift over 8 ft on a one-pipe system
  • Dirty oil plugging a small nozzle

Check in this order

  1. One-pipe no bypass plug. Two-pipe: bypass plug installed.
  2. Oil pressure at the burner inlet must not go over 3 psig. Install a pressure limiting device per NFPA 31.
  3. Gravity feed needs an anti-siphon valve in the supply line, or solenoid valve 2182602U in the pump-to-nozzle line, as backup oil shut-off.
  4. No valves in the return line.
  5. Tank more than 8 ft below the burner: two-pipe system, maybe a two-stage pump (check the pump maker's lift charts).
  6. Use heavy wall copper with flare fittings only. No compression fittings. No Teflon tape; use oil-resistant pipe dope.
  7. Two fusible-handle shutoff valves one at the tank, one near the burner ahead of the filter.
  8. Filter of 50 micron or finer near the burner. Below 0.75 GPH, add a 10 micron (or finer) secondary filter near the burner with a 50 micron primary near the tank.

Applies to: Beckett NX burner with GeniSys 7505 primary control on Weil-McLain Ultra Oil UO-3, UO-4, UO-5 (CV and DV)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Beckett NX Burner Manual for Weil-McLain Ultra Oil boilers (W-M 550-141-996/0321), Installing the oil tank and supply system p.8-9. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.