Choosing a boiler installation location

Vitodens 200-W B2HA

What is going on

Pick a heated indoor spot near a floor drain and as close to an outside wall as practical, so venting is easy to run. The wall must carry 155 lb (72 kg), the boiler filled with water. Ambient air must stay between 32°F (0°C) and 104°F (40°C). Keep existing ventilation openings open and do not let the boiler share air with other fuel-burning equipment in a way that blocks its combustion air.

Check in this order

  1. Confirm the room is heated and indoors, with a floor drain nearby.
  2. Check that the wall can hold 155 lb (72 kg) with the boiler full of water.
  3. Confirm ambient temperature stays between 32°F (0°C) and 104°F (40°C).
  4. Keep existing ventilation openings open and do not block combustion air for other appliances.
  5. Keep the boiler away from chemical sources (see contaminated air guide).

Applies to: Vitodens 200-W B2HA 45 and 60, boiler room placement

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HA 45, 60 Installation Instructions, p. 9. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.