Reinstall the burner assembly
What is going on
Refit the burner with the specified torques, then perform a gas leak test.
Check in this order
- Fit the burner and tighten the screws in a diagonal pattern to 132 lb.in (15 Nm).
- Fit the gas line connection with a new gasket and torque to 132 lb.in (15 Nm).
- Reconnect the electrical cables to the correct parts.
- Perform a gas leak test.
Applies to: Vitodens 222-F B2TB 19, 35, 68, 125
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 222-F B2TB service instructions, p. 22. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.