Strap-on flow sensor installation

Versatronik 200

What is going on

The immersion sensor can also be strapped to a pipe. When used for mixing valve sensing, place it on the pipe that carries the mixed temperature out of the mixing valve. Apply the supplied contact paste first.

Check in this order

  1. Choose the sensing location, on the mixed outlet if used with the mixing valve.
  2. Apply the supplied contact paste between sensor and pipe.
  3. Position the retaining cap over the sensor, with the wire through the open end.
  4. Fasten the cap and sensor with the supplied wire tie. Add ties or strapping on larger pipes.
  5. Tighten the strap and check that the sensor is securely fixed.
  6. Plug the sensor into the matching control socket.

Applies to: Flow sensor VF v (mixing valve extension kit)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 200 installation manual, p. 14. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.