Rinnai · Boiler troubleshooting
Wire DHW recirculation pump
What is going on
External recirculation pump connects to the Pump 4 terminal on the PC board when DHW recirculation is used. If four CH zone pumps are used, an external CH zone controller is required.
Check in this order
- Wire the external recirculation pump to the Pump 4 terminal on the PC board.
- If four CH zone pumps are used, add an external central heating zone controller.
- Set Parameter 09 to b (ON) to enable recirculation.
- Use an optional 24 V timer if timed recirculation is needed.
Applies to: I-Series Plus Condensing Combi Boiler
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 99. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.