Weil-McLain · Boiler troubleshooting

Gas valve leakage test (solenoids V1 and V2)

SVF 500/600 Series 1

What is going on

Test each solenoid one at a time using the gas valve test harness from the envelope kit. Follow the gas valve maker's leak test procedure as well. Do not connect a manometer to the gas valves, because blower vacuum can pull fluid into the gas line.

Check in this order

  1. Turn off power to the boiler.
  2. Get the gas valve test harness from the envelope kit.
  3. Disconnect the gas valve electrical harness.
  4. Plug the test harness between the gas valve and its electrical harness.
  5. Set both test harness rocker switches to ON.
  6. Turn power on and call for heat. Confirm a normal ignition sequence.
  7. Set both rockers to OFF, then turn one ON and call for heat. Only one indicator (V1 or V2) should light.
  8. Label that rocker V1 or V2 to match the indicator that lit.
  9. Label the other rocker with the other indicator.
  10. Use the rockers to run V1 or V2 separately per the manufacturer's leak test.
  11. When testing is done, turn power off, disconnect the test harness, and store it in the envelope.
  12. Reconnect the gas valve electrical harness. This must be done for normal operation.
  13. Turn power on and run an ignition cycle to confirm normal operation.

Applies to: SVF 500/600 gas valve with two solenoids

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF 500/600 Series 1 Boiler Manual, p. 101. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.