Weil-McLain · Boiler troubleshooting
Sidewall termination with separate vent and air pipes - location and clearances
What is going on
Clearances for the vent and air terminations on a sidewall. The air inlet must end in a down-turned elbow and the vent in an elbow pointed away from the air inlet.
Check in this order
- Keep the vent at least 6 ft from adjacent walls and 5 ft below any roof overhang.
- Keep the vent at least 7 ft above any public walkway and at least 3 ft above any forced air intake within 10 ft.
- Keep the vent 12 in below or to the side of any door, window or gravity inlet for appliances up to 150,000 BTU/hr. For appliances over 150,000 BTU/hr, use 48 in.
- Keep the vent at least 4 ft horizontally from any electric meter, gas meter, regulator or relief valve. Do not terminate above or below these within 4 ft horizontally.
- Set the air termination coupling at least 12 in below the vent termination and at least 12 in above grade or snow line.
- Keep at least 12 in between the vent pipe and an adjacent air inlet elbow (US installations). Keep both terminations at the same height on multi-boiler installs.
- Keep exposed vent pipe short. Limit exterior length so condensate cannot freeze and block the vent.
- Install braces no more than 24 in apart. Vent and air pipes may rise to 4 ft with no enclosure; beyond 4 ft use an insulated enclosure. In extremely cold climates use an insulated chase that allows inspection.
- Do not terminate above a door or window, under a deck, or in building corners, window wells, alcoves or other recessed areas.
- Do not connect any other appliance to the vent pipe or connect multiple boilers to one vent pipe.
Applies to: Ultra boilers using separate-pipe sidewall terminations
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain Ultra Series 4 boiler manual, p. 20-22. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.