Weil-McLain · Boiler troubleshooting
Boiler shut down or locked out by an external limit on J20
What is going on
J20 has two limit circuits, each shipped with a jumper. Pins 1-2 are manual reset: if a limit there opens, the boiler locks out, the alarm contacts close and someone has to reset the control. Pins 3-4 are auto reset: the boiler stops and starts again 150 seconds after the limit closes.
Likely causes
- External limit contact open
- Factory jumper missing or loose when no external limit is used
- Limit wired to the wrong J20 pair
Check in this order
- Safety first turn off power at the service switch before touching wiring. Gas-side work is for a qualified gas technician only.
- Check which J20 pair the external limit is wired to (1-2 manual reset, 3-4 auto reset).
- Check the limit itself is closed. The contacts must be isolated dry contacts.
- If no external limit is used on a pair, its factory jumper must be in place.
- Manual-reset pair the limit has to close first, then reset the control at the display.
- Auto-reset pair after the limit closes, give it 150 seconds to restart on its own.
- Remote alarm on J18 terminals 4-5 only closes on a manual lockout (rated 24 VAC or less, 0.5 A or less). It will not signal an auto-reset trip.
Applies to: ECO Tec 80, 110, 150, 199 Series 3 (heat only)
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain ECO Tec Series 3 Advanced Manual 550-100-600/1025, sec. Field wiring F. External limits, p.13-14; H. Alarm contacts, p.14. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.