Weil-McLain · Boiler troubleshooting

Boiler shut down or locked out by an external limit on J20

Weil-McLain ECO Tec Series 3

What is going on

J20 has two limit circuits, each shipped with a jumper. Pins 1-2 are manual reset: if a limit there opens, the boiler locks out, the alarm contacts close and someone has to reset the control. Pins 3-4 are auto reset: the boiler stops and starts again 150 seconds after the limit closes.

Likely causes

  • External limit contact open
  • Factory jumper missing or loose when no external limit is used
  • Limit wired to the wrong J20 pair

Check in this order

  1. Safety first turn off power at the service switch before touching wiring. Gas-side work is for a qualified gas technician only.
  2. Check which J20 pair the external limit is wired to (1-2 manual reset, 3-4 auto reset).
  3. Check the limit itself is closed. The contacts must be isolated dry contacts.
  4. If no external limit is used on a pair, its factory jumper must be in place.
  5. Manual-reset pair the limit has to close first, then reset the control at the display.
  6. Auto-reset pair after the limit closes, give it 150 seconds to restart on its own.
  7. Remote alarm on J18 terminals 4-5 only closes on a manual lockout (rated 24 VAC or less, 0.5 A or less). It will not signal an auto-reset trip.

Applies to: ECO Tec 80, 110, 150, 199 Series 3 (heat only)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain ECO Tec Series 3 Advanced Manual 550-100-600/1025, sec. Field wiring F. External limits, p.13-14; H. Alarm contacts, p.14. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.