Viessmann · Boiler troubleshooting

Boilers not communicating or not staging

Versatronik 300

What is going on

Boiler communication depends on unique LON addresses. A boiler that does not appear to be communicating is started last.

Likely causes

  • Duplicate LON address, including address 77
  • Boiler not reachable on the LON network

Check in this order

  1. Check that each boiler has a unique LON address, starting from 77.
  2. Check the B1 to B16 status screens for boilers that show no status or temperature.
  3. Check the Boiler config menu for the correct number of boilers.
  4. If all non-ECO lock boilers are running and set point is still not met, check the AUX output.

Applies to: Versatronik 300 cascade boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 300 Cascade Control manual, p. 30 and p. 32. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.