Viessmann · Boiler troubleshooting
Boilers not communicating or not staging
What is going on
Boiler communication depends on unique LON addresses. A boiler that does not appear to be communicating is started last.
Likely causes
- Duplicate LON address, including address 77
- Boiler not reachable on the LON network
Check in this order
- Check that each boiler has a unique LON address, starting from 77.
- Check the B1 to B16 status screens for boilers that show no status or temperature.
- Check the Boiler config menu for the correct number of boilers.
- If all non-ECO lock boilers are running and set point is still not met, check the AUX output.
Applies to: Versatronik 300 cascade boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 300 Cascade Control manual, p. 30 and p. 32. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.