Close-clearance install: boiler off on manual reset temperature switch
What is going on
Boilers installed with reduced clearances (alcove, closet, under a counter) use close clearance kit 386-500-050. Its manual reset temperature switch is mounted near the top of the enclosed space and wired in series with the thermostat. If the space gets too hot, the switch opens and the boiler gets no call for heat until it is reset.
Likely causes
- Not enough combustion/ventilation air into the enclosed space
- Flue pipe or jacket cap problem letting heat build up
- Burner combustion not set right
Check in this order
- Power off before working on the burner or wiring.
- Find the manual reset temperature switch near the top of the enclosure and check if it has tripped.
- Before resetting, check the two ventilation openings (near top and bottom of the space). Each should be 140 sq. in. per 1 GPH of input.
- Check that the jacket cap is on and the flue pipe clearances are kept.
- Set the burner with a combustion analyzer: zero smoke, over-fire draft -0.01 to -0.02 in. w.c., CO2 about 13% or less (this line is jumbled in the manual text, check the page).
- Reset the switch and run the boiler to design temperature. Watch that it does not trip again.
Applies to: WTGO-3 to WTGO-9 oil-fired cast iron boilers
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain WTGO Series 4 Boiler Manual 550-142-332/0225, Close clearance installation, Figures 26-27, p.34. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.