Viessmann · Boiler troubleshooting

Replacing the rotary damper and servomotor

Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

What is going on

Removing and refitting the air damper assembly on the burner.

Check in this order

  1. Disconnect the servomotor connector.
  2. Undo the 4 screws on the rotary damper retaining bracket (torque 13 lb.in / 1.5 Nm) and remove the damper with its bracket.
  3. Undo the 2 screws on the servomotor axis (torque 3 lb.ft / 4 Nm) and remove the servomotor.
  4. Release the articulated rod on the rotary damper with an open-ended wrench.
  5. Fit the new rotary damper, air pressure switch and servomotor in reverse order.
  6. Check that the rotary damper is fully open when the burner is off and when it is running. If not, adjust it with the articulated rod and check the servomotor settings.

Applies to: Vitocrossal 300 CA3B Dual Fuel burner air damper

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 Service Instructions, p. 64. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.