Hydrostatic pressure test of boiler water side
What is going on
Pressure test the boiler before connecting water or gas piping and before the electrical supply is connected. Relief valve is installed only after the test.
Check in this order
- Install 1/2 in reducer bushings (150/199), reducing tees and close nipples as shown in the piping figure, before the relief valve is fitted.
- Apply pipe dope sparingly to all fittings.
- Temporarily install a 3/4 in NPT pipe cap in the air elimination/relief valve water pipe connection.
- Install the pressure/temperature gauge on the reducing tee.
- Provide two shut-off valves and two close nipples (1 in NPT on 80/110, 1-1/4 in NPT on 150/199), plus the 3/4 in pipe cap.
- Close the boiler drain valve. Connect a hose from fresh water to the drain valve.
- Close isolation valve on the return, leave the supply isolation valve open, and crack the 3/4 in cap slightly.
- Slowly open the drain valve and fresh water supply to fill the boiler. Tighten the cap when water seeps from it.
- Continue filling until water flows from the supply isolation valve, then close it.
- Raise pressure to the test value (see setting table) by opening the drain valve as needed.
- Hold test pressure for 10 minutes. Do not leave the boiler unattended.
- Confirm pressure stays constant and check all joints for leaks. Repair any leak at once.
- Drain the boiler, remove the test fittings and cap, then install the relief valve, tee and elbow.
- Dry any water that got into electronic components, including the boiler control.
Applies to: ECO Tec 80/110/150/199 Series 3
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec Series 3 Boiler Manual, p. 17-18. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.