Viessmann · Boiler troubleshooting
External blocking via dry contact
What is going on
A closed contact shuts the burner down and switches off the boiler circuit pumps. The system has no frost protection while blocked, and the boiler is not held at its lower water temperature. Connect to plug avD (code 99, General group) or to extension EA1 (set 5D, 5E or 5F to 3 or 4). Optional temperature range settings are in coding address 1E.
Check in this order
- Use a potential-free dry contact.
- Connect to plug avD and set coding 99 (General group), or connect to extension EA1.
- If using EA1, set 5D, 5E or 5F (General group) to 3 or 4.
- Warn the owner that frost protection is off while blocked.
- For optional temperature range settings, check coding address 1E.
Applies to: External blocking contact
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 200 and 300-K Installation and Service, p. 21. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.