Navien · Boiler troubleshooting
Refilling the space heating side with the auto feeder
What is going on
The built-in automatic feeder fills the space heating side and stops on its own. Bleed air and check for leaks before restarting.
Check in this order
- Confirm the pump drain plug and DHW cold water inlet filter are installed and the drain fittings inside the unit are closed.
- Slowly open the water supply valve on the unit inlet, or open the supply at the water meter slowly if there is no valve.
- Check the unit for water leaks.
- Let the auto feeder fill the space heating side and stop.
- Check the manual air release to confirm the system filled properly.
- Bleed all air from the hot water lines, then close all hot water faucets.
- Turn power on to the unit.
- Open the gas valve.
- Open a hot water faucet to test. The unit should fire and run normally.
Applies to: CH combination boiler
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien CH User's Operation Manual, p. 34. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.