Viessmann · Boiler troubleshooting

Wire a 24V mixing valve adaptor

Vitotronic 300

What is going on

Use this when the mixing valve is driven through the 24V adaptor instead of a 120V actuator.

Check in this order

  1. Disconnect power to the control.
  2. Remove the plug connector gS from cables BK1, BK2 and BK3 of the 24V valve adaptor.
  3. Connect BK1, BK2 and BK3 to the DIN terminals for the required valve application, using the chart in the manual.
  4. Connect the black wire E of the mixing valve adaptor to a free terminal 14 to 17 on the DIN rail.
  5. Connect the valve actuator wires to the adaptor terminals as shown.
  6. Follow the mixing valve adaptor installation instructions for more detail.

Applies to: 24V mixing valve adaptor on Vitotronic 300 GW6B

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300, GW6B installation and service instructions, p. 35. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.