Viessmann · Boiler troubleshooting

Checking the DHW tank temperature sensor

Vitotronic 200-H

What is going on

Resistance check of the DHW tank temperature sensor against the displayed temperature.

Check in this order

  1. Disconnect one lead of the sensor cable.
  2. Measure the sensor resistance at the end of both leads.
  3. Compare the reading with the DHW temperature shown on the display (scan on p. 21).
  4. Check the installation and replace the sensor if the deviation is severe.

Applies to: DHW tank temperature sensor

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 200-H Installation and Service Instructions, p. 37. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.