Viessmann · Boiler troubleshooting
Fixed high limit test #1 (CSD-1 field test, pump unplugged)
What is going on
Field test of the manual reset fixed high limit. Only do this where required by law. Viessmann is not responsible for damage caused by overheating the system during the test.
Check in this order
- Confirm the boiler and boiler pump are in normal operating condition.
- Remove the cover at the back of the boiler control to reach the control plugs.
- In the extended menu, select Test mode, then flue gas test ON, and press OK.
- Wait for the burner to ignite and go to high fire.
- Once the burner has ignited, unplug the boiler pump plug (pump output 'sÖ') from the boiler control board, gently, using pliers.
- Watch the boiler temperature on the display. It rises, then the burner shuts off.
- The temperature should keep rising until it reaches 210°F (99°C), where the manual reset high limit trips and generates an F2 fault.
- If the limit is not reached, two minutes after the burner shuts off, briefly energize the boiler pump for a maximum of 1 second by plugging the pump plug back in.
Applies to: Models 112, 150, 399, 530
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA 112, 150, 399, 530 Service Instructions, p. 8. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.