Viessmann · Boiler troubleshooting

Installing the burner

Vitodens 100-W B1HE/B1KE

What is going on

Reverse of burner removal. Torque values are critical. Check all gas fittings for leaks before startup.

Check in this order

  1. Move the programming unit if needed.
  2. Insert the burner and tighten the screws diagonally to 35 lb.in (4 Nm).
  3. Fit the gas supply pipe with a new gasket and tighten to 22 lb.ft (30 Nm).
  4. Check the gas connections and shut-off valve for leaks.
  5. Reconnect the fan motor (2 plugs), ionization electrode, ignition unit and ground.
  6. Keep the gas pipe from twisting and make sure it does not touch any other component. Use the two-wrench method, not pliers.

Applies to: B1HE/KE 85/120 and 150/199

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 100-W B1HE/B1KE installation/service manual, p. 56. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.