Weil-McLain · Boiler troubleshooting

Masonry chimney used as a pipe chase

SlimFit Series 2

What is going on

A masonry chimney may only be used as a chase for the SlimFit vent and air pipe. No other appliance or fireplace may connect to it.

Likely causes

  • Other appliance or fireplace connected to the chimney
  • Offset or non-compliant chimney
  • Missing or unsealed inspection opening

Check in this order

  1. Run the vent and air pipe inside the chimney as a chase only, following this manual; seal all joints.
  2. Confirm the chimney is straight with no offsets.
  3. Confirm the chimney has a sealed access opening for inspecting its interior.
  4. Inspect the chimney and liner at least once a year for condition.

Applies to: SlimFit 1000-2000 Series 2

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 Boiler Manual, p. 23. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.