Weil-McLain · Boiler troubleshooting
Check water and antifreeze concentrations annually
What is going on
Check pH, inhibitor and antifreeze at least once a year.
Likely causes
- Inhibitor level may drop over time
- pH outside range may mean inhibitor is insufficient to prevent corrosion
Check in this order
- Test a sample of system water pH. It must be between 7.0 and 8.5.
- Or use the Sentinel inhibitor test kit to check the level.
- If pH is out of range or the kit shows low inhibitor, the inhibitor level may not prevent corrosion.
- Test antifreeze concentration and adjust as described in the antifreeze procedure.
- Check the inhibitor level again after any adjustment.
Applies to: SVF 500/600 Series 1
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SVF 500/600 Series 1 boiler manual, p. 94. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.