Weil-McLain · Boiler troubleshooting

Check water and antifreeze concentrations annually

SVF 500/600 Series 1

What is going on

Check pH, inhibitor and antifreeze at least once a year.

Likely causes

  • Inhibitor level may drop over time
  • pH outside range may mean inhibitor is insufficient to prevent corrosion

Check in this order

  1. Test a sample of system water pH. It must be between 7.0 and 8.5.
  2. Or use the Sentinel inhibitor test kit to check the level.
  3. If pH is out of range or the kit shows low inhibitor, the inhibitor level may not prevent corrosion.
  4. Test antifreeze concentration and adjust as described in the antifreeze procedure.
  5. Check the inhibitor level again after any adjustment.

Applies to: SVF 500/600 Series 1

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SVF 500/600 Series 1 boiler manual, p. 94. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.