Set up the boiler priorities in the Express Setup wizard
What is going on
Assign each input and output to the priority it serves, then choose the system type. Network priorities are set on the master boiler only.
Check in this order
- Open the Express Setup wizard and go to the priority screen.
- Pick which priority (1 to 4) each input or output will serve. Priority 1 is served first.
- Assign each priority as local (1 or 2, direct-piped to that boiler only) or network (1 or 2, any boiler on the network can satisfy it).
- Answer YES or NO to whether Network Priority 1 or 2 will be used if the screen asks.
- Select the system type for the priority (fan coil, finned tube baseboard, cast iron baseboard, cast iron radiator, radiant slab on grade, radiant thin slab, or custom).
- Set the target adjust method NONE (fixed target at max), ODT (outdoor reset, default), or 0-10V remote target.
- Enter max and min target temperatures and the reset points, or the voltage points if 0-10V is used.
- Set the boost time, pump run options, and the max/min on time on the master boiler.
- Confirm the sequencing, rotation and timer settings for the network.
Applies to: Multi-boiler and single boiler installations using the Express Setup wizard
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Series 2 Condensing Gas Boiler Advanced Manual, pp. 16-18. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.