Isolation heat exchanger piping for multiple boilers (Example C)

Evergreen Series 2

What is going on

The boilers are piped primary/secondary, with each boiler in a secondary loop. The heat exchanger shell side and the heating system side each need their own expansion tank. The heating system also needs its own relief valve. Piping, pumps and sizing for the heat exchanger come from the heat exchanger manufacturer.

Check in this order

  1. Pipe each boiler in a secondary loop, primary/secondary as shown.
  2. Give the heat exchanger shell-side circuit its own expansion tank.
  3. Give the heating system circuit its own expansion tank and its own relief valve.
  4. Size each circulator for the required flow.
  5. Get heat exchanger sizing and shell-side and tube-side piping from the heat exchanger manufacturer.
  6. Confirm tube-side flow and temperatures meet the heating system requirements.

Applies to: Example C multi-boiler with isolation heat exchanger

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Series 2 Condensing Gas Boiler Advanced Manual, p. 26-27. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.