Weil-McLain · Boiler troubleshooting

Steam boiler low water cutoff installation

EG / PEG Series 7

What is going on

Water line dimensions are measured from the bottom of the boiler section leg where it rests on the floor or foundation. Probe-type and float-type low water cutoffs are installed differently. Water feeders are not recommended as the primary control; use a low water cutoff with pump controller when a condensate receiver and feed pump are used.

Check in this order

  1. Measure water line dimensions from the bottom of the boiler section leg.
  2. For probe-type low water cutoffs, install as shown in Figure 24.
  3. For float-type low water cutoffs, install as shown in Figure 25.
  4. Install a blowdown line in the bottom of the cutoff per Figure 25 and the control maker's instructions.
  5. Pipe the blowdown line near the floor, close to a floor drain, to avoid burn hazards.
  6. Do not plug, valve or obstruct the blowdown line.
  7. Install the remaining controls per the control tapping table and Figure 4.
  8. Use a primary float LWCO or secondary manual reset LWCO with the primary probe LWCO as the control arrangement.

Applies to: EG and PEG steam boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: EG/PEG Series 7 boiler manual, p. 27. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.