Viessmann · Boiler troubleshooting

Remove burner and check burner gasket

Vitocrossal 300 CU3A

What is going on

Burner removal for inspection and cleaning. Hook the burner into its service retainer, not on its dome matrix.

Check in this order

  1. Switch off the main power and the ON/OFF switch at the control unit.
  2. Close the gas shut-off valve and secure against reopening.
  3. Unplug fan motor H, gas valve C, ionization electrode D and plug G.
  4. Disconnect the gas supply pipe E fitting and pull the air intake adaptor A.
  5. Remove the four nuts B and remove burner F, then hook it into service retainer L.
  6. Check burner gasket K for damage and replace if needed. Replace every 2 years.

Applies to: Vitocrossal 300 CU3A burner service

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 22. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.