No heat: check demand, power and safeties
What is going on
Work through these checks before replacing components when the boiler does not fire.
Likely causes
- No call for heat from thermostat, DHW aquastat or BMS
- Open external limit control
- Loose connector
- Gas pressure out of range or gas pressure switch tripped
Check in this order
- Space heating confirm the thermostat is calling and its contacts, including zone controls, are closed. Check for 24 VAC between thermostat wire nuts and ground.
- DHW confirm the tank aquastat is calling for heat.
- BMS systems confirm the BMS is calling for heat.
- Confirm all external limit controls are installed and closed, or temporarily jumpered for testing.
- Confirm connectors to the control module are fully plugged in at the module and at the originating controls and harnesses.
- Confirm gas pressure matches page 45 and that gas pressure switches are not tripped.
Applies to: SlimFit 1000-2000 MBH Series 2
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 94. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.