Weil-McLain · Boiler troubleshooting

No heat: check demand, power and safeties

SlimFit Series 2

What is going on

Work through these checks before replacing components when the boiler does not fire.

Likely causes

  • No call for heat from thermostat, DHW aquastat or BMS
  • Open external limit control
  • Loose connector
  • Gas pressure out of range or gas pressure switch tripped

Check in this order

  1. Space heating confirm the thermostat is calling and its contacts, including zone controls, are closed. Check for 24 VAC between thermostat wire nuts and ground.
  2. DHW confirm the tank aquastat is calling for heat.
  3. BMS systems confirm the BMS is calling for heat.
  4. Confirm all external limit controls are installed and closed, or temporarily jumpered for testing.
  5. Confirm connectors to the control module are fully plugged in at the module and at the originating controls and harnesses.
  6. Confirm gas pressure matches page 45 and that gas pressure switches are not tripped.

Applies to: SlimFit 1000-2000 MBH Series 2

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 94. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.