Clean the DHW filter (combi models only)
What is going on
If you have a combi and the hot water has gone weak or lukewarm, or the boiler will not see the flow, the first thing to look at is the DHW inlet filter and the flow meter turbine. They collect grit and scale, especially on new plumbing or after the city does work on the main. Cleaning them is a simple job, but the domestic side has to be valved off and drained first so you are not working under pressure. It takes about twenty minutes and often fixes the complaint outright.
Likely causes
- Debris or scale clogging the DHW inlet filter
- Grit jammed in the flow meter turbine so it spins slowly or not at all
- Recent plumbing work or water main disturbance sending sediment into the combi
- Hard water scale building up on the turbine over time
Check in this order
- Valve off and drain the combi DHW circuit before starting.
- Remove the clip on the flow meter, then remove the flow meter cap.
- Remove the flow meter turbine and check that it spins freely by hand.
- Remove the filter and clean it with a toothbrush and clean running water.
- Reinstall the filter, turbine and cap, making sure everything seats fully.
- Refill the DHW circuit and purge it following the filling and purging instructions.
- Restore gas and power, check for leaks at the work area, and run a hot water draw to confirm flow is back.
Applies to: TRX150 combi models
More boiler guides
Related
NTI error codes · NTI parts · NTI tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: NTI TRX150 manual, p. 98. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.