Fixed high limit test simulation #2
What is going on
Tests the fixed high limit with the boiler valve closed and the flow switch jumpered.
Check in this order
- Close the boiler valve and jumper across the flow switch.
- Run the boiler at high fire. In B2TB models, set coding address 06 to maximum so the coding card shuts it down.
- Keep the boiler temperature rising until the fixed high limit trips.
- Once the fixed high limit has tripped, slowly open the boiler valve to cool the boiler down safely.
Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 200-W B2HA 80 to 100, 285 to 352 service instructions, p. 8. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.