Viessmann · Boiler troubleshooting

Fixed high limit test simulation #2

Vitodens 200-W B2HA

What is going on

Tests the fixed high limit with the boiler valve closed and the flow switch jumpered.

Check in this order

  1. Close the boiler valve and jumper across the flow switch.
  2. Run the boiler at high fire. In B2TB models, set coding address 06 to maximum so the coding card shuts it down.
  3. Keep the boiler temperature rising until the fixed high limit trips.
  4. Once the fixed high limit has tripped, slowly open the boiler valve to cool the boiler down safely.

Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 200-W B2HA 80 to 100, 285 to 352 service instructions, p. 8. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.