Viessmann · Boiler troubleshooting
Check on-site gas connections for leakage
What is going on
Gas connections are checked during commissioning after the new gaskets are installed and before the boiler is put into operation. Check at the gauge connections. Do not let leak detection spray touch electrical contacts, as it can cause malfunction.
Check in this order
- Insert and tighten new gaskets at all detached on-site connections.
- Open the gas shut-off valve.
- Check the input-side sealing points of the combination gas valve for leakage.
- Put the boiler into operation.
- Check the output-side sealing points of the combination gas valve, the fan to burner plate seal and the fan to Venturi tube seal for leakage.
Applies to: Vitocrossal 300 CA3B Dual Fuel boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 17. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.