Space multiple boiler terminations

ECO Tec Series 3

What is going on

When more than one boiler vents through the same wall or roof, terminations must line up and keep minimum spacing.

Check in this order

  1. Set all vent pipes to terminate at the same height.
  2. Set all air pipes to terminate at the same height.
  3. Keep at least 12 in between the air intake edge and the vent pipe of an adjacent boiler.
  4. Keep maximum separation between vent and air pipes for each boiler as shown in the sidewall layout.
  5. For Canadian installs, follow CSA B149.1 or B149.2 and use a ULC S636 compliant vent kit.

Applies to: Multiple boiler vent and air terminations

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec Series 3 boiler manual, p. 33-35, 39-40. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.