Weil-McLain · Boiler troubleshooting
Remote target operation (0-10 VDC input)
What is going on
A remote analog signal sets the supply temperature for a priority.
Check in this order
- In the priority menu, set TARGET ADJUST to 0-10V.
- Set VOLTS FOR MIN TARGET for the desired minimum supply temperature.
- Set VOLTS FOR MAX TARGET for the desired maximum supply temperature.
Applies to: Any priority
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Series 2 Advanced Manual, p. 10-11. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.