Remote target operation (0-10 VDC input)

Evergreen Series 2

What is going on

A remote analog signal sets the supply temperature for a priority.

Check in this order

  1. In the priority menu, set TARGET ADJUST to 0-10V.
  2. Set VOLTS FOR MIN TARGET for the desired minimum supply temperature.
  3. Set VOLTS FOR MAX TARGET for the desired maximum supply temperature.

Applies to: Any priority

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Series 2 Advanced Manual, p. 10-11. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.