Install the boiler return mixing valve or modulating valve actuator (VD2/VD2A/CT3 only)
What is going on
A 120 V or 24 V valve adaptor is mounted on the DIN rail inside the connection enclosure. Operating time is set on coding address 40 (5 to 199 sec).
Check in this order
- Disconnect power to the control.
- Mount the 120 V or 24 V valve adaptor on the DIN rail inside the connection enclosure.
- Insert plug gS into socket gS on the control.
- Secure the cable with a tie (see page 21).
- Connect the black adaptor wire to terminal aBH on the DIN rail (terminal 8, 9 or 10).
- Connect the valve actuator wires to the adaptor terminals as shown in the figures.
- Set the valve operating time on coding address 40 (5 to 199 sec).
Applies to: Boiler return mixing valve or modulating valve actuator
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300 Installation and Service Instructions, p. 32. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.