Viessmann · Boiler troubleshooting

Install the boiler return mixing valve or modulating valve actuator (VD2/VD2A/CT3 only)

Vitotronic 300

What is going on

A 120 V or 24 V valve adaptor is mounted on the DIN rail inside the connection enclosure. Operating time is set on coding address 40 (5 to 199 sec).

Check in this order

  1. Disconnect power to the control.
  2. Mount the 120 V or 24 V valve adaptor on the DIN rail inside the connection enclosure.
  3. Insert plug gS into socket gS on the control.
  4. Secure the cable with a tie (see page 21).
  5. Connect the black adaptor wire to terminal aBH on the DIN rail (terminal 8, 9 or 10).
  6. Connect the valve actuator wires to the adaptor terminals as shown in the figures.
  7. Set the valve operating time on coding address 40 (5 to 199 sec).

Applies to: Boiler return mixing valve or modulating valve actuator

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 Installation and Service Instructions, p. 32. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.