Weil-McLain · Boiler troubleshooting
Low flame signal troubleshooting
What is going on
Use when the running flame signal stays low.
Likely causes
- Fouled ignition electrode
- Damaged electrode insulation
- Poor ground wiring
- Fouled heat exchanger
- Venting or combustion problem
Check in this order
- Remove and inspect the ignition electrode (p. 141).
- Clean the electrode if needed.
- If cleaning does not help and ground wiring and continuity are good, replace the ignition electrode.
- If the signal is still low, inspect the vent and air piping.
- Check combustion values.
- Inspect and clean the heat exchanger per the cover plate procedure (p. 151).
Applies to: ECO Tec Series 3 gas boilers
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec series 3 boiler manual, p. 142. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.