Viessmann · Boiler troubleshooting

Replace burner fan

Vitocrossal 200 CM2

What is going on

Burner fan and venturi assembly. Not for the CM2 186.

Check in this order

  1. Loosen the retaining clamp and disconnect the combustion air flex hose.
  2. Disconnect the gas line.
  3. Unplug fan plugs 100 and 100A. Disconnect the APS1 pressure switch tube from the venturi.
  4. Unplug plugs 35, 36, 87, 111 and 122 from the burner control. Remove the burner control cover to reach plugs 87 and 111.
  5. Remove the four M8 (13 mm hex) nuts that connect the fan to the burner door.
  6. Remove the six M8 (13 mm hex) bolts and washers that connect the fan to the venturi.
  7. Replace the two fan/burner door gaskets in their original order and orientation.
  8. Move the test port nipple from the old fan to the new fan. Tighten to 27 lb/in (3 Nm).
  9. Tighten the fan-to-venturi bolts to 53 lb/in (6 Nm) and the fan-to-burner door nuts to 53 lb/in (6 Nm). Keep the original orientation.
  10. Leak test the reconnected gas line.

Applies to: CM2 246, 311 and other models except CM2 186

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 39. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.