Power supply and grounding requirements
What is going on
Power supply, grounding and disconnect rules for the boiler. The boiler needs 120 VAC, 60 Hz from a grounded circuit. Do not use extension cords or adapter plugs. Gas or water piping must not be used as the ground.
Check in this order
- Use a grounded 120 VAC, 60 Hz circuit with a three-prong receptacle.
- Use the 5 ft (1.5 m) power cord supplied with the boiler. Do not use an extension cord or adapter.
- Do not cut or remove the ground pin on the plug.
- Use the ground locations provided inside the boiler.
- Remove the plug before any internal repairs, installation work, or changes to terminal wiring.
- Label all wires before disconnecting them for control service.
- Do not change the boiler wiring.
- Install a manual remote shutoff switch outside each boiler room door. Protect it from tampering.
- Verify correct operation after any service.
Applies to: I-Series Plus condensing combi boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rinnai I-Series Plus IP060160C installation manual, p. 66. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.