Weil-McLain · Boiler troubleshooting
Set bypass valves for primary/secondary low temperature piping
What is going on
Valve 7a mixes hot boiler outlet water with cooler return water. Valve 7b controls flow through the boiler secondary loop. Set them so the boiler return water is at least 130°F. Set the valves with the system cool, for the coldest expected water temperature (usually 60°F).
Likely causes
- Return water below 130°F
Check in this order
- Set the valves while the system is cool, for the coldest expected water temperature (usually 60°F).
- Start with valve 7a fully closed and valve 7b fully open.
- Slowly open valve 7a while closing valve 7b.
- Stop when gauge 8 reads 130°F while gauge 4a reads 60°F.
- If gauge 8 is not available, adjust until the boiler-mounted gauge reads at least 150°F with cold system return water (about 60°F).
Applies to: CGi-25 to CGi-8
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: CGi Series 5 boiler manual, p. 32. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.