Viessmann · Boiler troubleshooting
Block a lag boiler externally (aVD plug)
What is going on
Use the aVD plug to take a boiler out of the sequence from outside the control. Only applies to lag boilers.
Check in this order
- Use a potential-free contact only. A live contact causes short circuits or phase failure.
- To block the boiler, wire the contact to aVD.1/aVD.2 and close it. The boiler is removed from the sequence, the motorized isolation valve closes and the boiler circuit pump stops.
- Check that the other boilers take over the heat load.
- With the contact open, the boiler is integrated back into the sequence.
- To add the boiler as the last one in the sequence, wire the contact to aVD.2/aVD.3 and close it. The boiler is moved from its current position and started last.
- With the contact open, the boiler stays integrated in the current sequence.
- If all boilers are blocked or none is ready, the heating system has no frost protection.
Applies to: Vitotronic 300 GW6B, lag boilers, plug aVD
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300 GW6B installation and service manual, p. 40. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.