Viessmann · Boiler troubleshooting

Block a lag boiler externally (aVD plug)

Vitotronic 300 GW6B

What is going on

Use the aVD plug to take a boiler out of the sequence from outside the control. Only applies to lag boilers.

Check in this order

  1. Use a potential-free contact only. A live contact causes short circuits or phase failure.
  2. To block the boiler, wire the contact to aVD.1/aVD.2 and close it. The boiler is removed from the sequence, the motorized isolation valve closes and the boiler circuit pump stops.
  3. Check that the other boilers take over the heat load.
  4. With the contact open, the boiler is integrated back into the sequence.
  5. To add the boiler as the last one in the sequence, wire the contact to aVD.2/aVD.3 and close it. The boiler is moved from its current position and started last.
  6. With the contact open, the boiler stays integrated in the current sequence.
  7. If all boilers are blocked or none is ready, the heating system has no frost protection.

Applies to: Vitotronic 300 GW6B, lag boilers, plug aVD

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW6B installation and service manual, p. 40. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.