Viessmann · Boiler troubleshooting
Monthly owner/operator maintenance checks
What is going on
Monthly checks performed by the owner or operator.
Check in this order
- Check system pressure frequently.
- Confirm boiler control operates properly per the control instructions.
- Inspect all seals and retighten or replace as needed.
- Confirm combustion and ventilation air supply to and from the mechanical room is maintained.
- Confirm nothing blocks combustion ventilation air and no chemicals, garbage, gasoline, combustibles or flammable vapors are stored near the boiler.
- Check for water on the floor from the pressure relief valve discharge or any pipe, joint, valve or air vent.
- Test the pressure relief valve and confirm proper operation per its instructions.
- Check all operational high limits.
- If used, check condensate neutralization system operation and media condition and fill level.
- Check flue gas condensate pH (minimum 6.5).
- Check external vent pipe joints for moisture and check for ice on the vent or chimney outlet in winter.
Applies to: Vitocrossal 300 CA3B 2.5 to 6.0
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B service instructions, p. 163. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.