Dew-point protection with two-stage burner and Vitotronic control
What is going on
With a Vitotronic control in modulating mode, the burner must be able to reach full input to protect the boiler from dew-point corrosion.
Likely causes
- Boiler water falls below 140°F (60°C) and condensation forms
- Burner is limited to first stage in summer
Check in this order
- Set the first-stage minimum input of the two-stage burner as specified in the burner instructions.
- Do not limit the burner to first-stage operation during summer months.
- Confirm flue gas temperature at partial load is at least 248°F (120°C). Required value depends on chimney insulation and height.
- With a two-stage burner, the burner should switch to full input automatically when boiler water drops below 140°F (60°C).
Applies to: VD2-320 to VD2-1080 with two-stage burner and Vitotronic control
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 200 VD2 installation manual, p. 34. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.