Viessmann · Boiler troubleshooting
Outdoor temperature sensor mounting and wiring
What is going on
Mount the outdoor sensor on the north or northwest wall, away from openings and heat or water sources, and keep it unpainted and unplastered. Keep its cable away from line-voltage cable.
Check in this order
- Mount the sensor base 2 to 2.5 m (6.6 to 8.2 ft) above ground on the north or northwest wall.
- On multi-storey buildings, mount it in the upper part of the second floor.
- Keep the sensor away from windows, doors, air vents, balconies and drainage pipes.
- Do not paint or plaster over the sensor. If the wall is not yet plastered, allow for the plaster or remove the sensor first.
- Run the cable through the bushing, keeping it away from line-voltage cable.
- Connect the two wires to terminals 1 and 2 on the plug. The wires can be swapped.
- Insert the plug into socket 1 and apply strain relief.
Applies to: Outdoor temperature sensor, Vitotronic 300
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300 installation instructions, p. 13, p. 15. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.