Weil-McLain · Boiler troubleshooting
Zone valve zoning, general requirements
What is going on
Applies to all zone valve zoning applications. Use at least the minimum pipe size in Table 6 on all boiler loop piping to and from the primary/secondary connection. Do not use a closed-type expansion tank if connected to a water heater with an automatic vent. The control can run up to five circulators. For more than four zones, use an external zone controller.
Check in this order
- Check Table 6 pipe sizes for all boiler loop piping.
- Provide a system expansion tank per the expansion tank guidelines.
- If a DHW tank is connected directly, pipe it from the near-boiler piping to the DHW tank boiler connections.
- If using DHW as a zone, make sure no DHW tank is already connected to the boiler. Use the Advanced Manual to set TARGET MODULATION SENSOR to System Supply when system sensors are installed.
- Use Priority 1 for DHW only if DHW should turn off lower priorities. Use Priority 2 or 3 otherwise. Adjust MAX ON TIME to limit how long DHW priority lasts.
- Connect zone valve end switches to a space heating priority input to use default settings. Connect the system circulator to the matching output.
- Use isolation relays when connecting 3-wire zone valve end switches to inputs.
Applies to: Zone valve zoning
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF 500/600 Series 1 boiler manual, p. 23. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.