Zone valve zoning, general requirements

SVF 500/600 Series 1

What is going on

Applies to all zone valve zoning applications. Use at least the minimum pipe size in Table 6 on all boiler loop piping to and from the primary/secondary connection. Do not use a closed-type expansion tank if connected to a water heater with an automatic vent. The control can run up to five circulators. For more than four zones, use an external zone controller.

Check in this order

  1. Check Table 6 pipe sizes for all boiler loop piping.
  2. Provide a system expansion tank per the expansion tank guidelines.
  3. If a DHW tank is connected directly, pipe it from the near-boiler piping to the DHW tank boiler connections.
  4. If using DHW as a zone, make sure no DHW tank is already connected to the boiler. Use the Advanced Manual to set TARGET MODULATION SENSOR to System Supply when system sensors are installed.
  5. Use Priority 1 for DHW only if DHW should turn off lower priorities. Use Priority 2 or 3 otherwise. Adjust MAX ON TIME to limit how long DHW priority lasts.
  6. Connect zone valve end switches to a space heating priority input to use default settings. Connect the system circulator to the matching output.
  7. Use isolation relays when connecting 3-wire zone valve end switches to inputs.

Applies to: Zone valve zoning

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF 500/600 Series 1 boiler manual, p. 23. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.