NTI · Boiler troubleshooting
Venting below an overhang (sidewall snorkel)
What is going on
Sidewall snorkel venting under an overhang on an NTI TRX is the one that gets installers in trouble. The exhaust has to drop below the overhang by a set amount, and the terminations need proper spacing and snow clearance, or the boiler will recirculate exhaust or ice up. Local codes can be stricter than the manual, so check them first.
Likely causes
- Exhaust not low enough below the overhang
- Intake and exhaust terminations too close together
- Termination too close to grade or snow level
- Exhaust not extended far enough past the building
Check in this order
- For every 1 in of overhang, place the exhaust 1 in vertically below the overhang, with 12 in minimum
- Keep the minimum separation between exhaust and intake sidewall terminations required by local codes
- Keep at least 12 in above the highest expected snow level or grade, whichever is higher
- Extend the exhaust 12 to 24 in beyond the building
- Have the installation checked against local code before commissioning
Applies to: Sidewall snorkel venting
More boiler guides
Related
NTI error codes · NTI parts · NTI tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: NTI TRX150 manual, p. 42. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.