LON wiring in line topology

Vitotronic 300-K MW1S

What is going on

The Viessmann LON system uses line bus topology with an end-of-line resistor at both ends. Two wires plus shielding are always required; the wires are interchangeable.

Check in this order

  1. Connect each control unit or Vitocom in a line with Viessmann LON cable part no. 7143 495.
  2. Keep the cable run between devices at 7 m / 23 ft or less for direct cable connections.
  3. Fit an end-of-line resistor (part no. 7143 497) at both ends of the line. One is supplied with the Vitotronic 300-K MW1S.
  4. When using LON couplings (part no. 7143 496), no more than 3 cables may be used between two devices.
  5. Keep the wires and shielding intact on every connection.

Applies to: Vitotronic 300-K MW1S LON system

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitotronic 100 GC1 / Vitotronic 300-K MW1S installation and service instructions, p. 68. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.