Weil-McLain · Boiler troubleshooting

Check water system pressure and air vents

ECO Tec Series 3

What is going on

Confirm cold fill pressure and that system pressure stays in range while heating.

Likely causes

  • Expansion tank problem
  • Air in system

Check in this order

  1. Check cold fill pressure (usually around 12 PSIG).
  2. Watch system pressure as the boiler heats up. Excessive rise points to expansion tank sizing or performance.
  3. Remove air vent caps and briefly press the push valve to flush. Reinstall caps.
  4. Replace any leaking automatic air vents.
  5. Check water chemistry pH, hardness and inhibitor level (p. 130-131).

Applies to: ECO Tec Series 3 boiler systems

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec series 3 boiler manual, p. 141. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.