Weil-McLain · Boiler troubleshooting
Check water system pressure and air vents
What is going on
Confirm cold fill pressure and that system pressure stays in range while heating.
Likely causes
- Expansion tank problem
- Air in system
Check in this order
- Check cold fill pressure (usually around 12 PSIG).
- Watch system pressure as the boiler heats up. Excessive rise points to expansion tank sizing or performance.
- Remove air vent caps and briefly press the push valve to flush. Reinstall caps.
- Replace any leaking automatic air vents.
- Check water chemistry pH, hardness and inhibitor level (p. 130-131).
Applies to: ECO Tec Series 3 boiler systems
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec series 3 boiler manual, p. 141. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.