Navien · Boiler troubleshooting
Measuring inlet gas pressure at maximum firing rate
What is going on
Licensed professional only. Read the inlet gas pressure with a digital manometer at the pressure port while the boiler is at full fire.
Check in this order
- Close the manual gas valve on the supply line.
- Turn on the boiler and enter Special Operations (see the special operation tip for button sequence). Select 7. SH 2nd MAX.
- Press Back twice to return to normal operation and run space heating to purge gas from the line.
- Leave the boiler on until it shuts down for lack of gas, then turn it off.
- Remove the front cover (4 Phillips screws: 2 top, 2 bottom) and loosen the port screw shown in the manual.
- Connect the manometer to the pressure port. Zero the manometer first.
- Reopen the manual gas valve and check all fittings for leaks.
- Open several hot water taps fully to bring the boiler to maximum fire, and run other gas appliances in the home.
- Read the inlet pressure at maximum fire and compare it to the inlet gas pressure limits.
Applies to: NCB700 series
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NCB700 installation and operation manual, p. 57-58. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.