Weil-McLain · Boiler troubleshooting

Condensate line - sizing, pump and materials

SVF 500/600 Series 1

What is going on

Route condensate to drain or pump and keep the line open so it cannot back into the boiler.

Likely causes

  • Condensate freezes in the line
  • Condensate line is obstructed
  • Condensate backs up into the boiler

Check in this order

  1. Use 3/4 in PVC or CPVC pipe to route condensate to a drain or pump.
  2. If using a pump, select one approved for condensing boilers and furnaces, with an overflow switch.
  3. Provide an external power source for the pump.
  4. Size the pump for at least 10 GPH per boiler for both SVF 500 and SVF 600.
  5. When sizing the pump, include the total load of all SVF boilers connected to it.
  6. Keep the condensate line unobstructed so condensate flows freely. A frozen or blocked line can back up into the boiler and cause lockout.
  7. Use PVC and CPVC that meets ASTM D1785, F441 or D2665, with cement and primer to ASTM D2564 or F493. In Canada, use CSA or ULC certified pipe, fittings and cement.
  8. If local code requires, install a neutralizing filter. Condensate is slightly acidic, about pH 3.2 to 4.5. A Weil-McLain neutralizer kit is listed in the Parts section (p. 131).

Applies to: SVF 500/600 condensate drain and pump

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SVF 500/600 Series 1 boiler manual, p. 61. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.