Weil-McLain · Boiler troubleshooting
Set up the 0 to 10 VDC remote target input
What is going on
A 0 to 10 VDC signal adjusts the supply target temperature through the TARGET ADJUST setting. Using it disables Input 1 for heat calls.
Check in this order
- Connect the 0 to 10 VDC signal positive to P15 terminal 6 and common to terminal 5.
- Wire a dry contact heat demand to an unused input, since 0 to 10 VDC does not start a call for heat.
- Assign and set up the priority through the Wizard or the PRIORITY SETTINGS menu.
- Use Priority 2 for space heating. Set TARGET ADJUST to 0-10V.
- Set VOLTS FOR MAX to the voltage that calls for the highest target, and set SUPPLY MAX to that temperature.
- Set VOLTS FOR MIN to the voltage that calls for the lowest target, and set SUPPLY MIN to that temperature.
- Between the two voltage points, the target scales proportionally between SUPPLY MAX and SUPPLY MIN.
Applies to: SlimFit 550/750 Series 3 boiler
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 3 boiler manual, p. 56. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.