Set up the 0 to 10 VDC remote target input

SlimFit Series 3

What is going on

A 0 to 10 VDC signal adjusts the supply target temperature through the TARGET ADJUST setting. Using it disables Input 1 for heat calls.

Check in this order

  1. Connect the 0 to 10 VDC signal positive to P15 terminal 6 and common to terminal 5.
  2. Wire a dry contact heat demand to an unused input, since 0 to 10 VDC does not start a call for heat.
  3. Assign and set up the priority through the Wizard or the PRIORITY SETTINGS menu.
  4. Use Priority 2 for space heating. Set TARGET ADJUST to 0-10V.
  5. Set VOLTS FOR MAX to the voltage that calls for the highest target, and set SUPPLY MAX to that temperature.
  6. Set VOLTS FOR MIN to the voltage that calls for the lowest target, and set SUPPLY MIN to that temperature.
  7. Between the two voltage points, the target scales proportionally between SUPPLY MAX and SUPPLY MIN.

Applies to: SlimFit 550/750 Series 3 boiler

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 3 boiler manual, p. 56. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.