Viessmann · Boiler troubleshooting
Check strap-on or immersion supply/return sensor
What is going on
Check resistance of the supply or return temperature sensor and compare with the displayed temperature.
Likely causes
- Displayed temperature differs significantly from actual temperature
Check in this order
- Remove plug 2/17.
- Measure resistance at terminals 1 and 2, or 2 and 3 if a return sensor is fitted.
- Compare the reading with the resistance table.
- Compare the value with the displayed actual temperature (see scanning on page 23).
- If the value differs significantly, check installation and replace the sensor if needed.
Applies to: Strap-on and immersion temperature sensors
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 200-H HK1M installation and service instructions, p. 35. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.