Viessmann · Boiler troubleshooting

Check strap-on or immersion supply/return sensor

Vitotronic 200-H

What is going on

Check resistance of the supply or return temperature sensor and compare with the displayed temperature.

Likely causes

  • Displayed temperature differs significantly from actual temperature

Check in this order

  1. Remove plug 2/17.
  2. Measure resistance at terminals 1 and 2, or 2 and 3 if a return sensor is fitted.
  3. Compare the reading with the resistance table.
  4. Compare the value with the displayed actual temperature (see scanning on page 23).
  5. If the value differs significantly, check installation and replace the sensor if needed.

Applies to: Strap-on and immersion temperature sensors

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 200-H HK1M installation and service instructions, p. 35. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.