Viessmann · Boiler troubleshooting
Verify gas input by clocking the gas meter
What is going on
Time how long the boiler takes to burn a set amount of gas and compare with the nameplate input. Other gas appliances on the meter must be off during the test.
Check in this order
- Turn off all other gas appliances served by the meter.
- Time how many seconds the boiler takes to use 10 ft3 of gas.
- Confirm the heating value of the gas with the gas utility first.
- Calculate input (3600 x 10) divided by seconds gives ft3 per hour; multiply by heating value (Btu/ft3) to get Btu/h.
- Example a 199 model at 181 seconds per 10 ft3 with 1000 Btu/ft3 gives about 199,000 Btu/h, which is correct.
- An input 5% under the rating is acceptable. Do not overfire the boiler.
- Metric or low altitude formulas INPUT = (3600 / t) x 1000 with t in seconds per 1 ft3; or INPUT = (3600 x 0.01 x 1000 x 35.31) / T with T in seconds per 0.01 m3 of natural gas. These apply to low altitude only.
Applies to: Vitocrossal 300 CU3A 26 to 199 (low altitude)
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 27. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.