Viessmann · Boiler troubleshooting

Verify gas input by clocking the gas meter

Vitocrossal 300 CU3A

What is going on

Time how long the boiler takes to burn a set amount of gas and compare with the nameplate input. Other gas appliances on the meter must be off during the test.

Check in this order

  1. Turn off all other gas appliances served by the meter.
  2. Time how many seconds the boiler takes to use 10 ft3 of gas.
  3. Confirm the heating value of the gas with the gas utility first.
  4. Calculate input (3600 x 10) divided by seconds gives ft3 per hour; multiply by heating value (Btu/ft3) to get Btu/h.
  5. Example a 199 model at 181 seconds per 10 ft3 with 1000 Btu/ft3 gives about 199,000 Btu/h, which is correct.
  6. An input 5% under the rating is acceptable. Do not overfire the boiler.
  7. Metric or low altitude formulas INPUT = (3600 / t) x 1000 with t in seconds per 1 ft3; or INPUT = (3600 x 0.01 x 1000 x 35.31) / T with T in seconds per 0.01 m3 of natural gas. These apply to low altitude only.

Applies to: Vitocrossal 300 CU3A 26 to 199 (low altitude)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 27. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.