Viessmann · Boiler troubleshooting

Mixing valve moves the wrong way (flow temperature drops when valve is opened)

Vitodens 200-W B2HA

What is going on

During a manual test of the mixing valve on an extension kit, the flow temperature sensor reads lower instead of higher when the valve is set to Open. This means the motor is turning the wrong way or the valve set is fitted incorrectly.

Likely causes

  • Mixing valve motor rotating in the wrong direction
  • Mixing valve set incorrectly fitted

Check in this order

  1. Set the mixing valve manually to Open.
  2. Check that the flow temperature sensor reads a higher temperature.
  3. If the temperature drops, reverse the rotational direction of the mixing valve motor.
  4. If the temperature still drops, check that the mixing valve set is fitted correctly.

Applies to: Extension kit for heating circuit with mixing valve (accessory)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HA 45, 60 service instructions, p. 80. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.