Display blank and no response to call for heat

ECO Tec Series 3

What is going on

The control is not getting 24 VAC power.

Likely causes

  • Short circuit or incorrect wiring.
  • Blown 3 A low voltage fuse.
  • Transformer not outputting 24 VAC.

Check in this order

  1. Check wiring for shorts and correct it per the wiring diagram, including the transformer connection to the control.
  2. Check the 3 A low voltage fuse and replace it with the Parts section part if blown.
  3. If the fuse blows again, recheck wiring per the diagrams.
  4. Check transformer output for 24 VAC.
  5. Replace the transformer if it receives 120 VAC but outputs no 24 VAC.

Applies to: ECO Tec Series 3

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec Series 3 boiler manual, p. 163. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.